s7414-3dp,增加im153-1dp從站,出錯
鄭志武
發(fā)布于2012-11-14 17:23
52
0
標簽:
我們單位有一個s7-414-3dp的cpu下掛了連個im153-1(dp4號和5號)機架,現(xiàn)在想再繼續(xù)增加一個im153-1(dp,6號)機架。
6號機架中個通道為do32*24v,第二個通道為di32*24v.使用的上位機軟件為step7v5.5sp2,當硬件下下去之后,cpu就無法工作。診斷數(shù)據(jù)如下:
diagnosticbufferofmodulecpu414-3dp
orderno./descriptioncomponentversion
6es7414-3xj04-0ab0hardware2
---firmwarev4.1.0
rack:0
slot:3
serialnumber:svpt8378675
event1of112:eventid16#39c4
distributedi/os:stationfailure
addressoftheaffecteddpslave:stationnumber:5
dpmastersystemid:1
log.baseaddressofthedpslave:inputaddress:8186
log.baseaddressofthedpmaster:8191
requestedob:rackfailureob(ob86)
obnotfound,ordisabled,orcannotbestartedinthecurrentoperatingmode
externalerror,incomingevent
12:44:18.087pm11/13/2012
(coding:16#39c4fe56c0541fff1ffa0105)
event2of112:eventid16#38c7
distributedi/os:stationoperationalagain,buterror(s)inmoduleparameterassignment
addressoftheaffecteddpslave:stationnumber:5
dpmastersystemid:1
log.baseaddressofthedpslave:inputaddress:8186
log.baseaddressofthedpmaster:8191
requestedob:rackfailureob(ob86)
obnotfound,ordisabled,orcannotbestartedinthecurrentoperatingmode
externalerror,outgoingevent
12:44:18.086pm11/13/2012
(coding:16#38c7fe56c0541fff1ffa0105)
event3of112:eventid16#5961
parameterassignmenterrorinparametersfordistributeds7modules
outputaddress:544ofthemodulewithparameterassignmenterrors
errortype:slotconfiguredforcpuisnotoccupiedorisoccupiedbyaplaceholder,orastationhasfailedortheswitchedi/osystemhaslostitsredundancy.
datarecordnumber:0
operatingmode:stop(internal)
externalerror,incomingevent
12:44:18.084pm11/13/2012
(coding:16#5961ff04c17b007a82200005)
event4of112:eventid16#5961
parameterassignmenterrorinparametersfordistributeds7modules
outputaddress:528ofthemodulewithparameterassignmenterrors
errortype:slotconfiguredforcpuisnotoccupiedorisoccupiedbyaplaceholder,orastationhasfailedortheswitchedi/osystemhaslostitsredundancy.
datarecordnumber:0
operatingmode:stop(internal)
externalerror,incomingevent
12:44:18.083pm11/13/2012
(coding:16#5961ff04c17b007a82100005)
............
如果再次將5號機架的dp插頭撥到on位置,并重新下原來的組態(tài)(就是把6號從站的硬件組態(tài)刪除了),cpu就顯示一切正常。
但是就算是組態(tài)錯誤,為何錯誤是發(fā)生在原有的5號從站上面呢?
另外,ob85,0b86,ob121,ob122這些我都是有寫入cpu的。
請高手幫助分析下,原因何在,謝謝。
佳答案
1、新增加的6號dp從站,硬件撥碼地址是否正確
2、5號從站dp的終端電阻撥為off,新增的6號從站終端電阻撥為on
3、通訊速率和通訊距離的問題
對照下面看下:
9.6kbps到187.5kbps:1000米
500kbaud:400米
1.5mbaud:200米
3mbaud到12mbaud:100米
4、更該通訊方式。
讓cpu處于中間位置,dp接頭終端電阻撥為off,兩端的dp從站設(shè)備終端電阻撥為on,試一試!
5、注意硬件組態(tài)的型號和版本要和實際事物型號和版本相對應。